CONDUCTOR
Stranded bare copper conductor class 2 (IEC 60228) (tinned conductor and class 5 formation, on request)
SPECIAL TAPE
Mica-Glass
INSULATION
XLPE
IDENTIFICATION
- 1 Core black
- 2 Core blue-black
- 3 Core black-blue-brown
- 4 Core black-black-blue-brown
- 5 Core black numbered
FILLER AND INNER COVERING OR TAPE
LSZH
ARMOURING
Tinned or Bare Copper Wire Braid
OUTER SHEATH
SHF1
VOLTAGE RATING
0,6/1 kV
TEMP. RATING
- During operation: -20°C + 85°C
- During installation: -15°C + 60°C
MARKING
METALLURGICA BRESCIANA - YEAR - FR-HF-APC- .....x...... mm2 0,6/1 kV - IEC 332-3A - IEC 331
| N° OF CONDUCTOR | CROSS SECTIONAL AREA mm2 | APPROX OVERALL DIAMETER mm | APPROX CABLE WEIGHT Kg/Km | MIN BENDING RADIUS mm |
MAX CONDUC. RESISTANCE AT 20°C OHM/Km | CURRENT RATING AT 45°C A | REACTANCE AT 50 Hz OHM/Km |
12,10 7,41 4,61 3,08 |
17 24 32 41 |
0,113 0,107 0,101 0,097 |
|||||
| 2 | 1,5 2,5 4 6 |
11,7 12,5 13,5 15,3 |
220 260 310 430 |
71 75 83 92 |
|||
| 3 | 1,5 2,5 4 6 10 16 25 |
12,2 13,1 14,7 16,0 18,3 20,6 24,7 |
240 290 400 500 690 940 1300 |
74 79 89 96 110 121 146 |
12,10 7,41 4,61 3,08 1,83 1,15 0,73 |
14 20 27 34 47 63 84 |
0,099 0,093 0,087 0,082 0,078 0,07 0,076 |
4 |
1,5 | 13,1 | 270 | 79 | 12,10 | 14 | 0,106 |
| 7 | 1,5 | 15,6 | 420 | 94 | 12,10 | 10 | |
| 10 | 1,5 | 19,2 | 560 | 116 | 12,10 | 10 | |
| 14 | 1,5 | 20,7 | 690 | 125 | 12,10 | 9 | |
| 19 | 1,5 | 23,3 | 900 | 140 | 12,10 | 7 | |
| 24 | 1,5 | 26,8 | 1070 | 161 | 12,10 | 7 |
Note: Different sections are available on request.