CONDUCTOR
Solid Alloy - See table 1 for reference
INSULATION
PVC
LAY-UP
Cores are paired, pairs are twisted in reverse layer technique forming a concentric cable.
COLOUR CODE
See table 2 for Colour Code Identification
INDIVIDUAL SCREEN
Aluminium-backed polyester tape, with tinned copper drain wire 0,5 mm2
WRAPPING
Polyester binder tape.
COLLECTIVE SCREEN
Aluminium-backed polyester tape, with tinned copper drain wire 0,5 mm2
INNER SHEATH
PVC
ARMOURING
Galvanised steel wire braid
OUTER SHEATH
PVC
RATED VOLTAGE
300/500 V r.m.s
TEST VOLTAGE
1000 V r.m.s for 1' between conductor, and between conductors and screen/ armour
TEMP. RATING
- During operation: -30 °C + 70°C
- During installation: - 5°C + 50°C
| N° OF PAIRS | CROSS SECTIONAL AREA AWG | NOMINAL INSULATION THICKNESS mm | DIAMETER OF ARMOUR WIRE mm |
NOMINAL SHEATH THICKNESS mm |
APPROX OVERALL DIAMETER mm D | APPROX CABLE WEIGHT Kg/Km | MIN BENDING RADIUS = nxD |
| N | |||||||
15,6 17,5 20,6 26,3 28,8 35,2 |
365 450 625 1000 1250 1745 |
10 10 10 10 10 10 |
|||||
2 4 6 12 16 24 |
16 | 0,60 0,60 0,60 0,60 0,60 0,60 |
0,3 |
1,4 1,4 1,5 1,6 1,6 1,7 |
|||
2 4 6 12 16 24 |
20 | 0,60 0,60 0,60 0,60 0,60 0,60 |
0,3 |
1,4 1,4 1,5 1,6 1,6 1,7 |
13,8 15,3 17,9 22,6 24,6 29,9 |
282 340 460 710 860 1190 |
10 10 10 10 10 10 |
Note: Different number of pairs and Conductors Sizes are available upon request.