CONDUCTOR
Stranded bare copper wire
INSULATION
PVC
LAY-UP
Cores are paired, pairs are twisted in reverse layer technique forming a concentric cable. 2 pair cables are twisted in a star quad formation.
COLOUR CODE
Refer to table 2 for Colour Code.
WRAPPING
Polyester binder tape.
COLLECTIVE SCREEN
Aluminium-backed polyester tape, with tinned copper drain wire 0,5 mm2
INNER SHEATH
PVC
ARMOURING
Single layer of steel wires (SWA)
OUTER SHEATH
PVC
RATED VOLTAGE
300/500 V r.m.s
TEST VOLTAGE
1000 V r.m.s for 1' between conductor, and between conductors and screen / armour
TEMP. RATING
- During operation: -30 °C + 70°C
- During installation: - 5°C + 50°C
| N° OF PAIRS | CROSS SECTIONAL AREA mm2 | NOMINAL INSULATION THICKNESS mm | DIAMETER OF ARMOUR WIRE mm |
NOMINAL SHEATH THICKNESS mm | APPROX OVERALL DIAMETER mm D | APPROX CABLE WEIGHT Kg/Km | MIN BENDING RADIUS = nxD |
| N | |||||||
1,3 1,3 1,5 1,6 1,7 1,8 1,9 |
10,7 12,3 17,9 22,9 26,4 29,1 33,9 |
225 280 540 900 1250 1450 1900 |
12 12 12 12 12 12 12 |
||||
1 2(quad) 5 10 15 20 30 |
0,50 (16x0,20) | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
0,9 0,9 0,9 1,25 1,6 1,6 1,6 |
||||
1 2(quad) 5 10 15 20 30 |
0,75 (24x0,2) | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
0,9 0,9 1,25 1,6 1,6 1,6 2,0 |
1,3 1,4 1,5 1,7 1,8 1,8 2,0 |
11,7 12,9 19,8 25,3 28,2 31,3 37,5 |
240 310 700 1150 1400 1680 2500 |
12 12 12 12 12 12 12 |
1 2(quad) 5 10 15 20 30 |
1,00 (7x0,53) | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
0,9 0,9 1,25 1,6 1,6 1,6 2,0 |
1,4 1,4 1,6 1,8 1,9 2,0 2,1 |
12,9 14,3 22,1 28,4 32,2 35,7 42,5 |
300 400 880 1480 1910 2300 3330 |
12 12 12 12 12 12 12 |
Note: Cables with higher or different number of pairs are available.