CONDUCTOR
Stranded bare copper wires.
INSULATION
PVC
LAY-UP
Cores are paired, pairs are twisted in reverse layer technique forming a concentric cable.
COLOUR CODE
Refer to table 2 for Colour Code.
INDIVIDUAL SCREEN
Aluminium-backed polyester tape, with tinned copper drain wire 0,5 mm2
WRAPPING
Polyester binder tape.
COLLECTIVE SCREEN
Aluminium-backed polyester tape, with tinned copper drain wire 0,5 mm2
OUTER SHEATH
PVC
RATED VOLTAGE
300/500 V r.m.s
TEST VOLTAGE
1000 V r.m.s for 1' between conductor, and between conductors and screen / armour
TEMP. RATING
- During operation: -30 °C + 70°C
- During installation: - 5°C + 50°C
| N° OF PAIRS | CROSS SECTIONAL AREA mm2 | NOMINAL INSULATION THICKNESS mm | NOMINAL SHEATH THICKNESS mm |
APPROX OVERALL DIAMETER mm D | APPROX CABLE WEIGHT Kg/Km | MIN BENDING RADIUS = nxD |
| N | ||||||
10,40 13,40 18,60 21,70 24,10 28,80 |
120 220 385 550 720 1000 |
10 10 10 10 10 10 |
||||
2 5 10 15 20 30 |
0,50 (16x0,20) | 0,60 0,60 0,60 0,60 0,60 0,60 |
1,10 1,20 1,30 1,50 1,50 1,70 |
|||
2 5 10 15 20 30 |
0,75 (24x0,2) | 0,60 0,60 0,60 0,60 0,60 0,60 |
1,10 1,20 1,30 1,50 1,70 2 |
11,20 14,40 20,10 23,50 26,50 31,90 |
150 265 460 670 900 1280 |
10 10 10 10 10 10 |
2 5 10 15 20 30 |
1,00 (7x0,53) | 0,60 0,60 0,60 0,60 0,60 0,60 |
1,20 1,30 1,50 1,70 1,70 2 |
13,30 17,20 24,20 28,20 31,40 37,80 |
215 390 700 1020 1340 1910 |
10 10 10 10 10 10 |
Note: Cables with higher or different number of pairs are available.