CONDUCTOR
Stranded bare copper wires.
INSULATION
PVC
LAY-UP
Cores are paired, pairs are twisted in reverse layer technique forming a concentric cable. 2 pair cables are twisted in a star quad formation.
COLOUR CODE
Refer to table 2 for Colour Code.
WRAPPING
Polyester binder tape.
COLLECTIVE SCREEN
Aluminium-backed polyester tape, with tinned copper drain wire 0,5 mm2
OUTER SHEATH
PVC
RATED VOLTAGE
300/500 V r.m.s
TEST VOLTAGE
1000 V r.m.s for 1' between conductor, and between conductors and screen / armour
TEMP. RATING
- During operation: -30 °C + 70°C
- During installation: - 5°C + 50°C
| N° OF PAIRS | CROSS SECTIONAL AREA mm2 | NOMINAL INSULATION THICKNESS mm | NOMINAL SHEATH THICKNESS mm |
APPROX OVERALL DIAMETER mm D | APPROX CABLE WEIGHT Kg/Km | MIN BENDING RADIUS = nxD |
| N | ||||||
6,50 7,00 12,00 16,50 19,50 21,50 25,50 |
55 70 165 280 400 510 720 |
10 10 10 10 10 10 10 |
||||
1 2(quad) 5 10 15 20 30 |
0,50 (16x0,20) | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
0,80 0,80 1,10 1,20 1,30 1,30 1,50 |
|||
1 2(quad) 5 10 15 20 30 |
0,75 (24x0,2) | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
0,80 0,80 1,20 1,30 1,30 1,50 1,70 |
6,70 7,40 13,10 18,00 20,80 32,50 28,20 |
60 80 210 360 500 670 945 |
10 10 10 10 10 10 10 |
1 2(quad) 5 10 15 20 30 |
1,00 (7x0,53) | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
0,80 0,90 1,20 1,30 1,50 1,50 1,70 |
7,50 8,80 15,20 21,50 25,00 28,00 33,50 |
80 125 310 560 820 1070 1530 |
10 10 10 10 10 10 10 |
Note: Cables with higher or different number of pairs are available.