CONDUCTOR
Solid/stranded bare copper wires.
INSULATION
PE
LAY-UP
Cores are paired, pairs are twisted in reverse layer technique forming a concentric cable. 2 pair cables are twisted in a star quad formation.
COLOUR CODE
Refer to table 1 for Colour Code
WRAPPING
Polyester binder tape
COLLECTIVE SCREEN
Aluminium-backed polyester tape, with tinned copper drain wire 0,5 mm2
INNER SHEATH
PE
ARMOURING
Single layer of steel wires (SWA)
OUTER SHEATH
PVC
RATED VOLTAGE
300/500 V r.m.s
TEST VOLTAGE
1000 V r.m.s for 1' between conductor, and between conductors and screen / armour
TEMP. RATING
- During operation: -30 °C + 70°C
- During installation: - 5°C + 50°C
| N° OF PAIRS | CROSS SECTIONAL AREA mm2 | NOMINAL INSULATION THICKNESS mm | DIAMETER OF ARMOUR WIRE mm | NOMINAL SHEATH THICKNESS mm |
APPROX OVERALL DIAMETER mm D | APPROX CABLE WEIGHT Kg/Km | MIN BENDING RADIUS = nxD |
| N | |||||||
10,1 10,8 15,4 20,3 22,5 25,4 28,9 |
200 225 390 690 810 1130 1400 |
12 12 12 12 12 12 12 |
|||||
1 2(quad) 5 10 15 20 30 |
0,50 (1x0,80) | 0,50 0,50 0,50 0,50 0,50 0,50 0,50 |
0,9 0,9 0,9 1,25 1,25 1,6 1,6 |
1,3 1,3 1,4 1,6 1,6 1,7 1,8 |
|||
1 2(quad) 5 10 15 20 30 |
0,5 (16x0,20) | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
0,9 0,9 0,9 1,25 1,6 1,6 1,6 |
1,3 1,3 1,5 1,6 1,7 1,8 1,9 |
10,7 11,5 16,9 22,5 26 28,2 32,5 |
210 245 450 760 1100 1280 1600 |
12 12 12 12 12 12 12 |
1 2(quad) 5 10 15 20 30 |
1,00 (1x1,13) | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
0,9 0,9 1,25 1,25 1,6 1,6 1,6 |
1,3 1,4 1,5 1,7 1,8 1,8 2,0 |
11,2 12,4 18,9 24,1 28 30,8 35,6 |
240 290 640 940 1340 1610 2050 |
12 12 12 12 12 12 12 |
1 2(quad) 5 10 15 20 30 |
1,50 (7x0,53) | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
0,9 0,9 1,25 1,60 1,60 2,00 2,00 |
1,4 1,4 1,6 1,8 1,9 2 2,1 |
12,5 13,6 21,1 28,5 32,2 36 41,8 |
280 340 780 1350 1720 2290 2950 |
12 12 12 12 12 12 12 |
Note: Cables with higher or different number of pairs are available.