CONDUCTOR
Solid/stranded bare copper wires.
INSULATION
PE
LAY-UP
Cores are paired, pairs are twisted in reverse layer technique forming a concentric cable.
COULOUR CODE
Refer to table 1 for Colour Code
INDIVIDUAL SCREEN
Aluminium-backed polyester tape, with tinned copper drain wire 0,5 mm2
WRAPPING
Polyester binder tape
COLLECTIVE SCREEN
Aluminium-backed polyester tape, with tinned copper drain wire 0,5 mm2
OUTER SHEATH
PVC
RATED VOLTAGE
300/500 V r.m.s
TEST VOLTAGE
1000 V r.m.s for 1' between conductor, and between conductors and screen / armour
TEMP. RATING
- During operation: -30 °C + 70°C
- During installation: - 5°C + 50°C
| N° OF PAIRS | CROSS SECTIONAL AREA mm2 | NOMINAL INSULATION THICKNESS mm | NOMINAL SHEATH THICKNESS mm |
APPROX OVERALL DIAMETER mm D | APPROX CABLE WEIGHT Kg/Km | MIN BENDING RADIUS = nxD |
| N | ||||||
8,90 12,00 16,20 18,50 20,50 24,80 |
95 190 315 440 565 820 |
10 10 10 10 10 10 |
||||
2 5 10 15 20 30 |
0,50 (1x0,80) | 0,50 0,50 0,50 0,50 0,50 0,50 |
0,90 1,20 1,20 1,30 1,30 1,50 |
|||
2 5 10 15 20 30 |
0,5 (16x0,20) | 0,60 0,60 0,60 0,60 0,60 0,60 |
1,10 1,20 1,30 1,50 1,50 1,70 |
10,40 13,40 18,60 21,70 24,10 28,80 |
115 200 355 510 650 920 |
10 10 10 10 10 10 |
2 5 10 15 20 30 |
1,00 (1x1,13) |
0,60 0,60 0,60 0,60 0,60 0,60 |
1,10 1,20 1,30 1,50 1,70 2,00 |
11,40 14,60 20,50 23,90 27,00 32,50 |
140 270 475 690 920 1325 |
10 10 10 10 10 10 |
2 5 10 15 20 30 |
1,50 (7x0,53) | 0,60 0,60 0,60 0,60 0,60 0,60 |
1,20 1,30 1,50 1,70 1,70 2,00 |
13,20 17,20 24,20 28,20 31,40 37,80 |
200 360 650 950 1230 1770 |
10 10 10 10 10 10 |
Note: Cables with higher or different number of pairs are available.