CONDUCTOR
Stranded bare copper conductor
INSULATION
PVC
LAY-UP
Cores are paired, pairs are twisted in reverse layer technique forming a concentric cable.
COLOUR CODE
Refer to table 2 for Colour Code.
INDIVIDUAL SCREEN
Aluminium-backed polyester tape, with tinned copper drain wire 0,5 mm2
WRAPPING
Polyester binder tape.
COLLECTIVE SCREEN
Aluminium-backed polyester tape, with tinned copper drain wire 0,5 mm2
INNER SHEATH
PVC
ARMOURING
Single layer of steel wires (SWA)
OUTER SHEATH
PVC
RATED VOLTAGE
300/500 V r.m.s
TEST VOLTAGE
1000 V r.m.s for 1' between conductor, and between conductors and screen / armour
TEMP. RATING
- During operation: -30 °C + 70°C
- During installation: - 5°C + 50°C
| N° OF PAIRS | CROSS SECTIONAL AREA mm2 | NOMINAL INSULATION THICKNESS mm | DIAMETER OF ARMOUR WIRE mm |
NOMINAL SHEATH THICKNESS mm | APPROX OVERALL DIAMETER mm D | APPROX CABLE WEIGHT Kg/Km | MIN BENDING RADIUS = nxD |
| N | |||||||
1,5 1,6 1,6 1,7 1,9 1,9 |
16,8 20,9 27,8 31,1 34,00 39,8 |
460 750 1290 1580 1860 2670 |
12 12 12 12 12 12 |
||||
2 5 10 15 20 30 |
0,50 (16x0,20) | 0,60 0,60 0,60 0,60 0,60 0,60 |
0,9 0,9 1,25 1,6 1,6 1,6 |
||||
2 5 10 15 20 30 |
0,75 (24x0,2) | 0,60 0,60 0,60 0,60 0,60 0,60 |
0,9 1,25 1,6 1,6 1,6 2 |
1,5 1,6 1,7 1,7 1,9 2 |
17,5 21,8 29,2 33,0 33,1 37,2 |
500 830 1390 1780 2350 3080 |
12 12 12 12 12 12 |
2 5 10 15 20 30 |
1,00 (7x0,53) | 0,60 0,60 0,60 0,60 0,60 0,60 |
0,9 1,25 1,6 1,6 1,6 1,25 |
1,7 1,7 1,7 1,8 1,9 2 |
20,1 24,9 33,00 37,9 41,5 50,1 |
700 1150 1790 2520 2970 4390 |
12 12 12 12 12 12 |