CONDUCTOR
Solid/stranded bare copper wires.
INSULATION
PE
LAY-UP
Cores are paired, pairs are twisted in reverse layer technique forming a concentric cable. 2 pair cables are twisted in a star quad formation.
COLOUR CODE
Refer to table 1 for Colour Code
WRAPPING
Polyester binder tape
COLLECTIVE SCREEN
Aluminium-backed polyester tape, with tinned copper drain wire 0,5 mm2
OUTER SHEATH
PVC
RATED VOLTAGE
300/500 V r.m.s
TEST VOLTAGE
1000 V r.m.s for 1' between conductor, and between conductors and screen / armour
TEMP. RATING
- During operation: -30 °C + 70°C
- During installation: - 5°C + 50°C
| N° OF PAIRS | CROSS SECTIONAL AREA mm2 | NOMINAL INSULATION THICKNESS mm | NOMINAL SHEATH THICKNESS mm |
APPROX OVERALL DIAMETER mm D | APPROX CABLE WEIGHT Kg/Km | MIN BENDING RADIUS = nxD |
| N | ||||||
5,50 6,20 10,60 14,40 16,60 18,60 21,90 |
40 55 130 220 300 400 540 |
10 10 10 10 10 10 10 |
||||
1 2(quad) 5 10 15 20 30 |
0,50 (1x0,80) | 0,50 0,50 0,50 0,50 0,50 0,50 0,50 |
0,80 0,80 1,10 1,20 1,20 1,30 1,30 |
|||
1 2(quad) 5 10 15 20 30 |
0,5 (16x0,20) | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
0,80 0,80 1,10 1,20 1,30 1,30 1,50 |
7,20 9,90 11,40 13,70 17,10 19,10 23,60 |
45 60 145 245 350 450 625 |
10 10 10 10 10 10 10 |
1 2(quad) 5 10 15 20 30 |
1,00 (1x1,13) |
0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
0,80 0,80 1,20 1,20 1,30 1,50 1,50 |
7,50 10,60 12,20 14,70 18,70 20,70 26,50 |
60 85 210 360 520 690 960 |
10 10 10 10 10 10 10 |
1 2(quad) 5 10 15 20 30 |
1,50 (7x0,53) | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
0,80 0,90 1,20 1,30 1,50 1,50 1,70 |
8,20 12,20 14,20 17,10 21,50 24,50 30,50 |
75 120 290 510 750 980 1400 |
10 10 10 10 10 10 10 |
Note: Cables with higher or different number of pairs are available.