CONDUCTOR
Stranded bare copper conductor
INSULATION
PVC
LAY-UP
Cores are paired, pairs are twisted in reverse layer technique forming a concentric cable.
COLOUR CODE
Black-white with black cores numbered for pairs identification
INDIVIDUAL SCREEN
Aluminium-backed polyester tape, with tinned copper drain wire 0,5 mm2
WRAPPING
Polyester binder tape
COLLECTIVE SCREEN
Aluminium-backed polyester tape, with tinned copper drain wire 0,5 mm2
INNER SHEATH
PVC
ARMOURING
Single layer of steel wires (SWA)
OUTER SHEATH
PVC
RATED VOLTAGE
300/500 V r.m.s
TEST VOLTAGE
1000 V r.m.s for 1' between conductor, and between conductors and screen / armour
TEMP. RATING
- During operation: -30 °C + 70°C
- During installation: - 5°C + 50°C
| N° OF PAIRS | CROSS SECTIONAL AREA mm2 | NOMINAL INSULATION THICKNESS mm | DIAMETER OF ARMOUR WIRE mm | NOMINAL SHEATH THICKNESS mm |
APPROX OVERALL DIAMETER mm D | APPROX CABLE WEIGHT Kg/Km | MIN BENDING RADIUS = nxD |
| N | |||||||
13,8 15,3 17,6 22,5 24,6 30,3 33,8 |
330 410 530 920 1095 1620 2050 |
12 12 12 12 12 12 12 |
|||||
2 4 6 12 16 24 36 |
0,50 | 0,50 0,50 0,50 0,50 0,50 0,50 0,50 |
0,8 0,8 0,8 1,25 1,25 1,6 1,6 |
1,5 1,5 1,6 1,6 1,7 1,9 1,9 |
|||
2 4 6 12 16 24 36 |
0,75 | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
0,8 0,8 0,8 1,25 1,6 1,6 2,0 |
1,5 1,5 1,6 1,7 1,7 1,9 2,0 |
15,3 17,1 19,8 25,9 28,9 34,8 40,5 |
390 495 650 1150 1530 2040 2950 |
12 12 12 12 12 12 12 |
2 4 6 12 16 24 36 |
1,00 | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
0,8 0,8 1,25 1,6 1,6 2,0 2,0 |
1,5 1,7 1,7 1,7 1,8 1,9 2,0 |
15,9 18,3 22 28 30,7 38,2 43 |
420 560 885 1490 1715 2560 3315 |
12 12 12 12 12 12 12 |
2 4 6 12 16 24 36 |
1,50 | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
0,8 0,8 1,25 1,6 1,6 2,0 2,5 |
1,6 1,6 1,7 1,9 1,9 2,2 2,3 |
17,4 19,6 23,6 30,8 33,6 42 48,5 |
480 635 1025 1735 2045 3100 4410 |
12 12 12 12 12 12 12 |