

CONDUCTOR
Stranded bare copper wires
INSULATION
PVC
LAY-UP
Cores are paired, pairs are twisted in reverse layer technique forming a concentric cable. 2 pair cables are twisted in a star quad formation.
COLOUR CODE
Black-white with black cores numbered for pairs identification
WRAPPING
Polyester binder tape
COLLECTIVE SCREEN
Aluminium-backed polyester tape, with tinned copper drain wire 0,5 mm2
INNER SHEATH
PVC
ARMOURING
Single layer of steel wires (SWA)
OUTER SHEATH
PVC
RATED VOLTAGE
300/500 V r.m.s
TEST VOLTAGE
1000 V r.m.s for 1' between conductor, and between conductors and screen / armour
TEMP. RATING
- During operation: -30 °C + 70°C
- During installation: - 5°C + 50°C
| N° OF PAIRS | CROSS SECTIONAL AREA mm2 | NOMINAL INSULATION THICKNESS mm | DIAMETER OF ARMOUR WIRE mm | NOMINAL SHEATH THICKNESS mm |
APPROX OVERALL DIAMETER mm D | APPROX CABLE WEIGHT Kg/Km | MIN BENDING RADIUS = nxD |
| N | |||||||
10,2 11,2 14,2 16,2 20,9 22,6 27,5 31 |
200 245 350 450 780 910 1340 1680 |
12 12 12 12 12 12 12 12 |
|||||
1 2 4 6 12 16 24 36 |
0,50 | 0,50 0,50 0,50 0,50 0,50 0,50 0,50 0,50 |
0,8 0,8 0,8 0,8 1,25 1,25 1,6 1,6 |
1,3 1,4 1,4 1,5 1,6 1,6 1,7 1,9 |
|||
1 2 4 6 12 16 24 36 |
0,75 | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
0,8 0,8 0,8 0,8 1,25 1,25 1,6 2,0 |
1,3 1,4 1,5 1,6 1,6 1,7 1,8 1,9 |
11 12,2 16 18,3 23,7 25,9 31,7 37 |
230 290 435 565 980 1165 1715 2470 |
12 12 12 12 12 12 12 12 |
1 2 4 6 12 16 24 36 |
1,00 | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
0,8 0,8 0,8 0,8 1,25 1,6 1,6 2,0 |
1,3 1,4 1,5 1,6 1,7 1,7 1,9 2,0 |
11,4 12,7 16,7 19,3 25,2 28 34,2 39,3 |
250 310 480 630 1100 1480 2000 2820 |
12 12 12 12 12 12 12 12 |
1 2 4 6 12 16 24 36 |
1,50 | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
0,8 0,8 0,8 1,25 1,6 1,6 2,0 2,0 |
1,4 1,5 1,6 1,7 1,8 1,9 2,0 2,2 |
12,2 13,6 18,1 22 28,1 30,8 38,2 43,2 |
280 360 505 905 1490 1795 2670 3480 |
12 12 12 12 12 12 12 12 |