CONDUCTOR
Stranded bare copper wires
INSULATION
PVC
LAY-UP
Cores are paired, pairs are twisted in reverse layer technique forming a concentric cable.
COLOUR CODE
Black-white with black cores numbered for pairs identification
INDIVIDUAL SCREEN
Aluminium-backed polyester tape, with tinned copper drain wire 0,5 mm2
WRAPPING
Polyester binder tape
COLLECTIVE SCREEN
Aluminium-backed polyester tape, with tinned copper drain wire 0,5 mm2
OUTER SHEATH
PVC
RATED VOLTAGE
300/500 V r.m.s
TEST VOLTAGE
1000 V r.m.s for 1' between conductor, and between conductors and screen / armour
TEMP. RATING
- During operation: -30 °C + 70°C
- During installation: - 5°C + 50°C
| N° OF PAIRS | CROSS SECTIONAL AREA mm2 | NOMINAL INSULATION THICKNESS mm | NOMINAL SHEATH THICKNESS mm |
APPROX OVERALL DIAMETER mm D | APPROX CABLE WEIGHT Kg/Km | MIN BENDING RADIUS = nxD |
| N | ||||||
9,45 10,90 12,90 17,20 19,20 23,90 27,80 |
95 145 215 360 470 670 995 |
10 10 10 10 10 10 10 |
||||
2 4 6 12 16 24 36 |
0,50 | 0,50 0,50 0,50 0,50 0,50 0,50 0,50 |
1,10 1,10 1,10 1,20 1,20 1,30 1,50 |
|||
2 4 6 12 16 24 36 |
0,75 | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
1,10 1,10 1,10 1,20 1,30 1,50 1,70 |
10,90 12,70 15,20 20,40 22,90 28,80 33,50 |
120 190 285 485 645 935 1380 |
10 10 10 10 10 10 10 |
2 4 6 12 16 24 36 |
1,00 | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
1,20 1,20 1,30 1,30 1,30 1,50 1,70 |
11,85 13,80 16,50 22,00 24,50 30,90 36,00 |
140 225 350 580 755 1100 1630 |
10 10 10 10 10 10 10 |
2 4 6 12 16 24 36 |
1,50 | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
1,20 1,30 1,30 1,50 1,50 2,00 2,00 |
12,90 15,50 18,50 24,50 27,60 35,30 40,50 |
170 290 435 760 995 1490 2150 |
10 10 10 10 10 10 10 |