CONDUCTOR
Stranded bare copper wires
INSULATION
XLPE
LAY-UP
Cores are paired, pairs are twisted in reverse layer technique forming a concentric cable. 2 pair cables are twisted in a star quad formation.
COLOUR CODE
Black-white with black cores numbered for pairs identification
WRAPPING
Polyester binder tape
COLLECTIVE SCREEN
Aluminium-backed polyester tape, with tinned copper drain wire 0,5 mm2
OUTER SHEATH
PVC
RATED VOLTAGE
300/500 V r.m.s
TEST VOLTAGE
1000 V r.m.s for 1' between conductor, and between conductors and screen / armour
TEMP. RATING
-During operation: -30 °C + 70°C
- During installation: - 5°C + 50°C
| N° OF PAIRS | CROSS SECTIONAL AREA mm2 | NOMINAL INSULATION THICKNESS mm | NOMINAL SHEATH THICKNESS mm | APPROX OVERALL DIAMETER mm D |
APPROX CABLE WEIGHT Kg/Km | MIN BENDING RADIUS = nxD |
| N | ||||||
50 65 110 160 265 340 475 690 |
10 10 10 10 10 10 10 10 |
|||||
1 2 4 6 12 16 24 36 |
0,50 | 0,50 0,50 0,50 0,50 0,50 0,50 0,50 0,50 |
1,00 1,00 1,00 1,10 1,20 1,20 1,30 1,50 |
6,00 6,80 9,8 11,80 15,60 17,20 21,60 25,00 |
||
1 2 4 6 12 16 24 36 |
0,75 | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
1,00 1,00 1,00 1,10 1,20 1,30 1,30 1,50 |
6,80 7,80 11,40 13,70 18,40 20,60 25,60 29,70 |
60 85 145 220 360 480 665 985 |
10 10 10 10 10 10 10 10 |
1 2 4 6 12 16 24 36 |
1,00 | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
1,00 1,00 1,00 1,10 1,30 1,30 1,50 1,50 |
7,20 8,25 12,20 14,70 19,80 22,00 27,80 31,90 |
66 100 170 260 450 580 840 1200 |
10 10 10 10 10 10 10 10 |
1 2 4 6 12 16 24 36 |
1,50 | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
1,10 1,10 1,10 1,10 1,30 1,50 1,70 2,00 |
8,00 9,20 13,50 12,20 21,90 24,50 31,50 36,30 |
85 130 230 340 595 800 1155 1720 |
10 10 10 10 10 10 10 10 |