CONDUCTOR
Stranded bare copper wire
INSULATION
Silicon rubber
LAY-UP
Cores are paired, pairs are twisted in reverse layer technique forming a concentric cable. 2 pair cables are twisted in a star quad formation.
COLOUR CODE
Any colour combination may be used subject to agreement between the purchaser and the manufacturer.
WRAPPING
Polyester binder tape.
COLLECTIVE SCREEN
Aluminium-backed polyester tape, with tinned copper drain wire 0,5 mm2
INNER SHEATH
Thermoplastic Compound
ARMOURING
Single layer of steel wires (SWA)
OUTER SHEATH
PVC
RATED VOLTAGE
300/500 V r.m.s
TEST VOLTAGE
1000 V r.m.s for 1' between conductor, and between conductors and screen/ armour
TEMP. RATING
- During operation: -30 °C + 70°C
- During installation: - 5°C + 50°C
| N° OF PAIRS | CROSS SECTIONAL AREA mm2 | NOMINAL INSULATION THICKNESS mm | DIAMETER OF ARMOUR WIRE mm |
NOMINAL SHEATH THICKNESS mm |
APPROX OVERALL DIAMETER mm D | APPROX CABLE WEIGHT Kg/Km | MIN BENDING RADIUS = nxD |
| N | |||||||
10,8 12 16 18,4 22,6 24,8 29 |
210 260 420 540 750 910 1200 |
12 12 12 12 12 12 12 |
|||||
1 2 4 6 12 16 24 |
0,50 | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
0,8 0,8 0,8 0,8 0,8 0,8 0,8 |
1,3 1,4 1,5 1,6 1,7 1,8 1,8 |
|||
1 2 4 6 12 16 24 |
0,75 | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
0,8 0,8 0,8 0,8 0,8 0,8 1,25 |
1,3 1,4 1,5 1,6 1,7 1,8 1,8 |
11,2 12,4 16,8 19,4 24 26,4 31,8 |
230 285 460 600 800 1050 1600 |
12 12 12 12 12 12 12 |
1 2 4 6 12 16 24 |
1,00 | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
0,8 0,8 0,8 0,8 0,8 0,8 1,25 |
1,4 1,4 1,5 1,6 1,8 1,8 2 |
11,7 13 17,6 20 25,4 27,5 33,7 |
245 310 510 660 980 1160 1810 |
12 12 12 12 12 12 12 |
1 2 4 6 12 16 24 |
1,50 | 0,70 0,70 0,70 0,70 0,70 0,70 0,70 |
0,8 0,8 0,8 0,8 1,25 1,25 1,25 |
1,4 1,4 1,6 1,7 1,9 1,9 2,1 |
13 14,7 20 23 30,6 33,3 39,5 |
300 390 640 845 1530 1820 2450 |
12 12 12 12 12 12 12 |