CONDUCTOR
Stranded bare copper wires.
INSULATION
Silicon rubber
LAY-UP
Cores are paired, pairs are twisted in reverse layer technique forming a concentric cable. 2 pair cables are twisted in a star quad formation.
COLOUR CODE
Any colour combination may be used subject to agreement between the purchaser and the manufacturer.
WRAPPING
Polyester binder tape.
COLLECTIVE SCREEN
Aluminium-backed polyester tape, with tinned copper drain wire 0,5 mm2
OUTER SHEATH
PVC
RATED VOLTAGE
300/500 V r.m.s
TEST VOLTAGE
1000 V r.m.s for 1' between conductor, and between conductors and screen/ armour
TEMP. RATING
- During operation: -30 °C + 70°C
- During installation: - 5°C + 50°C
| N° OF PAIRS | CROSS SECTIONAL AREA mm2 | NOMINAL INSULATION THICKNESS mm | NOMINAL SHEATH THICKNESS mm |
APPROX OVERALL DIAMETER mm D | APPROX CABLE WEIGHT Kg/Km | MIN BENDING RADIUS = nxD |
| N | ||||||
6,6 7,5 11,5 13,6 17,6 19,6 23,8 |
50 70 140 210 330 430 610 |
10 10 10 10 10 10 10 |
||||
1 2 4 6 12 16 24 |
0,50 | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
0,8 0,8 1,1 1,2 1,2 1,3 1,5 |
|||
1 2 4 6 12 16 24 |
0,75 | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
0,8 0,8 1,1 1,2 1,3 1,3 1,5 |
7 8 12,2 14,6 19 21,2 25,7 |
60 85 170 255 415 530 760 |
10 10 10 10 10 10 10 |
1 2 4 6 12 16 24 |
1,00 | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
0,8 0,9 1,2 1,2 1,3 1,3 1,5 |
7,3 8,6 13 15,3 20,2 22,3 27,2 |
65 100 200 290 480 620 890 |
10 10 10 10 10 10 10 |
1 2 4 6 12 16 24 |
1,50 | 0,70 0,70 0,70 0,70 0,70 0,70 0,70 |
0,9 1,1 1,2 1,2 1,5 1,5 1,7 |
8,6 10,3 15,2 18 24,3 27 32,8 |
90 150 275 410 715 920 1330 |
110 10 10 10 10 10 10 |