CONDUCTOR
Stranded bare copper wire.
INSULATION
Double layer: Mica Tape + XLPE
LAY-UP
Cores are paired, pairs are twisted in reverse layer technique forming a concentric cable. 2 pair cables are twisted in a star quad formation.
COLOUR CODE
Black-white with black cores numbered for pairs identification
WRAPPING
Polyester binder tape.
COLLECTIVE SCREEN
Aluminium-backed polyester tape, with tinned copper drain wire 0,5 mm2
INNER SHEATH
Thermoplastic Compound
ARMOURING
Single layer of steel wires (SWA)
OUTER SHEATH
PVC
RATED VOLTAGE
300/500 V r.m.s
TEST VOLTAGE
1000 V r.m.s for 1' between conductor, and between conductors and screen/ armour
TEMP. RATING
- During operation: -30 °C + 70°C
- During installation: - 5°C + 50°C
| N° OF PAIRS | CROSS SECTIONAL AREA mm2 | NOMINAL INSULATION THICKNESS mm | DIAMETER OF ARMOUR WIRE mm |
NOMINAL SHEATH THICKNESS mm |
APPROX OVERALL DIAMETER mm D | APPROX CABLE WEIGHT Kg/Km | MIN BENDING RADIUS = nxD |
| N | |||||||
11 14,5 15,8 18 22,2 24,2 29,6 |
220 370 450 550 800 830 1350 |
12 12 12 12 12 12 12 |
|||||
1 2 4 6 12 16 24 |
0,50 | 0,50 0,50 0,50 0,50 0,50 0,50 0,50 |
0,8 0,8 0,8 0,8 0,8 0,8 1,25 |
1,3 1,4 1,4 1,5 1,6 1,6 1,7 |
|||
1 2 4 6 12 16 24 |
0,75 | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
0,8 0,8 0,8 0,8 0,8 0,8 1,25 |
1,3 1,4 1,5 1,6 1,6 1,7 1,8 |
11,5 15,3 17,2 20 25 27,4 33,6 |
230 410 500 670 940 1200 1570 |
12 12 12 12 12 12 12 |
1 2 4 6 12 16 24 |
1,00 | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
0,8 0,8 0,8 0,8 0,8 1,25 1,25 |
1,3 1,4 1,5 1,6 1,7 1,7 1,9 |
12 16,1 18,2 21 26,5 30 35,7 |
260 475 580 770 1100 1360 1880 |
12 12 12 12 12 12 12 |
1 2 4 6 12 16 24 |
1,50 | 0,60 0,60 0,60 0,60 0,60 0,60 0,60 |
0,8 0,8 0,8 0,8 1,25 1,25 1,25 |
1,4 1,5 1,6 1,7 1,8 1,9 2 |
13,6 18 20 22,7 29,7 32,6 38,8 |
305 560 690 890 1450 1780 2420 |
12 12 12 12 12 12 12 |