Auxiliary Pilot Cables - ESI 09.6

multipair Al/PEt collectively screened, SWA armoured;
Auxiliary Pilot Cables - ESI 09.6

CONDUCTOR

Solid bare copper conductor

INSULATION

PE

LAY-UP

Cores are paired, pairs are twisted in reverse layer technique forming a concentric cable.

COLOUR CODE

Black-white with black cores numbered for pairs identification.

WRAPPING

Polyester binder tape.

COLLECTIVE SCREEN

Aluminium-backed polyester tape, with tinned copper drain wire 0,5 mm2

INNER SHEATH

PE

ARMOURING

Single layer of steel wires (SWA)

OUTER SHEATH

PVC

RATED VOLTAGE

300/500 V r.m.s

TEST VOLTAGE

1000 V r.m.s for 1' between conductor, and between conductors and screen/ armour

TEMP. RATING

- During operation: -30 °C + 70°C

- During installation: - 5°C + 50°C

N° OF PAIRS CROSS SECTIONAL AREA mm2 NOMINAL INSULATION THICKNESS mm

DIAMETER OF ARMOUR WIRE mm

NOMINAL SHEATH THICKNESS mm

APPROX OVERALL DIAMETER mm D APPROX CABLE WEIGHT Kg/Km MIN BENDING RADIUS = nxD
N

20,2

27

34,2

725

1260

2150

10

10

10

5

10

20

1,50

0,60

0,60

0,60

1,25

1,6

2,0

1,6

1,8

2,0

5

10

20

2,5

0,60

0,60

0,60

1,25

1,6

2,0

1,7

1,9

2,0

23

31,5

39,7

930

1670

2830

10

10

10

Note: Different number of pairs and individually screened cables are available upon request

 

 

 


The data included in the present catalogue are merely indicative; Metallurgica Bresciana S.p.A. reserves to itself the right to change them at its own discretion and in any moment.
© Metallurgica Bresciana S.p.A. Manufacturer of Precision Special Electric Cables and Optical Fibre Cables