CONSTRUCTION
CONDUCTOR
Tinned copper stranded, concentric construction.
INSULATION
Double layer of e-beam crosslinked polyolefin.
Colours: black, white(ivory), red, green, blue, yellow.
MAIN DATA FOR UL 3289 CABLES - 600V
| CROSS SECTION | CROSS SECTION | CONDUCTOR CONSTRUCTION | OUTER DIAMETER | CONDUCTOR RESISTANCEAT 20°C | INSULATION RESISTANCE A 20°C | WEIGHT | |
| min | g/m | ||||||
| AWG | mm2 | n x Фmm | max | max | |||
| mm | Ω/km | MΩ• Km | |||||
26 24 22 20 18 16 13 10 |
0,14 0,22 0,34 0,59 1,00 1,50 2,50 4,65 |
7x0,16 7x0,20 7x0,25 19x0,20 19x0,25 19x0,32 37x0,28 37x0,40 |
1,10 1,20 1,30 1,50 1,81 2,10 2,61 3,51 |
140 88,60 56,10 32,30 20,30 14,50 8,20 4,02 |
5000 4000 3000 2000 1800 1400 1050 850 |
3 4 5 7 11 15 25 46 |
|
Operating voltage (Uο/U) : 450/750 V
Test voltage : 2500V c.a.
Operating temperature : -40 + 125 ץC
Halogenhydric gasses content ( IEC60754-1): 0,3% max
Degree of acidity of gasses (IEC60754-2):
acidity : pH 4,3 min
conductivity: 10 uS/mm max
Smoke optical density (IEC61034): 1,5 max
Flam retardancy : IEC 60332-1